Skip links

UNO-PS/1AC/24DC/150W Single-Phase DIN Rail Power Supply (24V Industrial Power Supply, AC to DC Converter )

71010 2000 int 04 lg
  • 24V DC Output Voltage
  • 6.25 Amps
  • 150 Watts
  • Single phase AC Input
  • Input Voltage Range: 85 ... 264 V AC

Jetzt unverbindlich anfragen!

Preise, Verfügbarkeit oder individuelle Beratung unverbindlich anfragen.

[elfsight_form_builder id=”1″]

Overview

The UNO-PS/1AC/24DC/150W Industrial Power Supply is a rugged AC to DC Converter built to meet the high stability and efficiency expectations of industrial, machine automation and process control environments. This Switching (switch mode) Power Supply ensures a regulated output voltage even in the event of voltage fluctuations in the power supply network. With all required safety certifications to support ITE (Information Technology Equipment), ruggedized packaging, extended operating temperatures, high peak load capabilities and high isolation voltages, the UNO Industrial Power Supply is designed to meet the needs of your industrial application.

Adjustable Output Voltage Range of 24 to 28 V DC

Using the rotary potentiometer on the front face of the UNO-PS/1AC/24DC/150W power supply, the output voltage can be optimally adjusted to meet specific application environment requirements. For example, you can easily adjust to compensate for a voltage drop caused by a long cable length.

Industrial operating temperature of -25°C to +70°C

Equipment found in traffic management, oil and gas pipelines, weather tracking, industrial and outdoor applications must function in temperatures that cannot be supported by a commercial power supplies. With an operating temperature of -25°C to +70°C, the UNO-PS/1AC/24DC/150W Industrial Power Supply is ideal for use with equipment subjected to harsh environments and severe temperatures.

High efficiency up to 94% and no load power consumption <0.3W

Compared with other products on the market, the UNO Industrial Power Supply provides excellent energy savings. With a very low no load power consumption (below .3 W) and 94% efficiency at nominal load, just a small amount of electrical energy is converted into undesired heat energy making this a very ECO friendly power supply.

Ideal application environments for an UNO-PS/1AC/24DC/150W DIN Rail Power Supply

  • automated production process
  • industrial control, automation, assembly, and test equipment
  • building control, security and surveillance, and climate control systems.
  • power countless industrial automation devices such as sensors, controllers and valves

Other reasons to choose the UNO-PS/1AC/24DC/150W Industrial Power Supply

  • 37 mm wide DIN Rail mount narrow housing
  • Voltage Isolation input/output: 4 kV AC
  • LED indicator for voltage out failure: If the output voltage is below the operational range, the LED turns off.
  • Protections: Short-circuit, Overload, Over voltage, Over-temperature
  • High MTBF (Mean Time Between Failure) values ensure maximum availability
  • IEC Protection Class II Power Supply


Hardware Specs

Environmental Product Compliance
REACH SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
General
Net weight 0.5 kg
Efficiency typ. 91 % (120 V AC)
typ. 94 % (230 V AC)
Insulation voltage input/output 4 kV AC (type test)
3 kV AC (routine test)
Protection class II (in closed control cabinet)
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 868000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: 0 mm horizontally, 30 mm vertically
Standards and Regulations
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise immunity EN 61000-6-2:2005
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz … 1 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1.4 GHz … 2 GHz
Test field strength 3 V/m (Test Level 2)
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-6-3
EN 61000-4-6
Frequency range 0.15 MHz … 80 MHz
Voltage 10 V (Test Level 3)
Standards/regulations EN 61000-4-11
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Safety of transformers EN 61558-2-16
Standard – Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV) and EN 60204 (PELV)
Standard – Safe isolation DIN VDE 0100-410
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz … 150 Hz, 2.3g, 90 min.
Approval – requirement of the semiconductor industry with regard to mains voltage dips EN 61000-4-11
Information technology equipment – safety (CB scheme) CB Scheme
Connection data, input
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3
Output data
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 24 V DC … 28 V DC ±1 %
Nominal output current (IN) 6.25 A (-25 °C … 55 °C)
Derating 55 °C … 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series No
Feedback resistance < 35 V DC
Protection against surge voltage on the output ≤ 35 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 40 mVPP (with nominal values)
Output power 150 W
Typical response time < 1 s
Maximum power dissipation in no-load condition < 1.2 W
Power loss nominal load max. < 9.7 W
Dimensions
Width 37 mm
Height 130 mm
Depth 125 mm
Weight per piece 500.0 GRM
Input data
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 85 V AC … 264 V AC
Current consumption 1.66 A (100 V AC)
0.68 A (240 V AC)
Nominal power consumption 164.7 VA
Inrush surge current < 50 A (typical)
Mains buffering typ. 20 ms (120 V AC)
typ. 20 ms (230 V AC)
Input fuse 2.5 A (slow-blow, internal)
Choice of suitable circuit breakers 6 A … 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.97
Type of protection Transient surge protection
Protective circuit/component Varistor
Connection data, onput
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 8 mm
Screw thread M3
Ambient conditions
Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Approvals
 
  • cULus Listed
  • cULus Recognized
  • EAC
  • UL Recognized
  • cUL Recognized
  • cUL Listed
  • IECEE CB Scheme
  • UL Listed


Diagrams

UNO-PS/1AC Industrial Power Supply Block Diagram
 
UNO-PS/1AC Industrial Power Supply Block Diagram
 

Return to top of page